PRODUCT LINES

Restaurant Systems
FEATURES
Low pH Agent
Proven Design
Reliable Cartridge Operated
Aesthetically Appealing
UL Listed - Meets Requirements of UL 300
APPLICATION
The Ansul R-102 Restaurant Fire Suppression System is an automatic, pre-engineered,
fire suppression system designed to protect the following areas associated with cooking
equipment; ventilating equipment including hoods, ducts, plenums, and filters; fryers;
griddles and range tops; upright, natural charcoal, or chain-type broilers; electric, lava
rock, mesquite or gas-radiant char-broilers and woks.
The system is ideally suitable for use in restaurants, hospitals, nursing homes, hotels,
schools, airports, and other similar facilities.
Use of the R-102 system is limited to interior applications only. The regulated release
and tank assemblies must be mounted in an area where the air temperature will not fall
below 32 oF (0 oC) or exceed 130 oF (54 oC).
The system must be designed and installed within the guidelines of the UL Listed Design,
Installation, Recharge, and Maintenance Manual.
SYSTEM DESCRIPTION
The restaurant fire suppression system is a pre-engineered, wet chemical,
cartridge-operated, regulated pressure type with a fixed nozzle agent distribution
network. It is listed with Underwriters Laboratories, Inc. (UL).
The system is capable of automatic detection and actuation and/or remote manual
actuation. Additional equipment is available for mechanical or electrical gas line
shut-off applications.
The detection portion of the fire suppression system allows for automatic detection by
means of specific alloy treated fusible links, which, when the temperature exceeds the
rating of the link, the link separates, allowing the regulated release to actuate. A
system owner's guide is available containing basic information pertaining to system
operation and maintenance. A detailed technical manual is also available including system
description, design, installation, recharge, and maintenance procedures, plus additional
equipment installation and resetting instructions.
The system is installed and serviced by authorized distributors that are trained by the
manufacturer. The basic system consists of an ANSUL AUTOMAN regulated release assembly
which includes a regulated release mechanism and a wet chemical storage tank housed within
a single enclosure. Nozzle blow-off caps, detectors, cartridges, agent, fusible links, and
pulley elbows are supplied in separate packages in the quantities needed for fire
suppression system arrangements.
Additional equipment includes remote manual pull station, mechanical and electrical gas
valves, pressure switches, and electrical switches for automatic equipment and gas line
shut-off. Accessories can be added such as alarms, warning lights, etc., to installations
when required.
Tanks can be used in multiple arrangements to allow for larger hazard coverage. Each
tank is limited to a listed maximum amount of flow numbers.
COMPONENT DESCRIPTION
Wet Chemical Agent - The extinguishing agent is
a potassium carbonate, potassium acetate-based formulation designed for rapid flame
knockdown and foam securement of grease related fires. It is available in plastic
containers with instructions for wet chemical handling and usage.
Agent Tank - The agent tank is installed in a
stainless steel enclosure or wall bracket. The tank is deep drawn carbon steel finished in
red enamel.
Tanks are available in two sizes: 1.5 gallon (5.7 L) and 3.0 gallon (11.4 L). The tanks
have a working pressure of 100 psi (6.9 bar), a test pressure of 300 psi (20.7 bar), and a
minimum burst pressure of 600 psi (41.4 bar).
The tank includes an adaptor/tube assembly. The adaptor is chrome-plated steel with a
1/4 in. NPT female gas inlet and a 3/8 in. NPT female agent outlet. The adaptor also
contains a bursting disc seal which prevents the siphoning of agent up the pipe during
extreme temperature variations.
Regulated Release Mechanism - The regulated
release mechanism is a spring-loaded, mechanical/pneumatic type capable of providing the
expellant gas supply to one or two agent tanks, depending on the capacity of the gas
cartridge used. It contains a factory installed regulator deadset at 100 psi (6.9 bar)
with an internal relief of approximately 145 psi (10.0 bar). It has automatic actuation
capabilities by a fusible link detection system and remote manual actuation by a
mechanical pull station.
The regulated release mechanism contains a release assembly, regulator, expellant gas
hose, and agent storage tank housed in a stainless steel enclosure with cover. The
enclosure contains knock-outs for 1/2 in. conduit. The convert contains an opening for a
visual status indicator.
It is compatible with mechanical gas shut-off devices; or, when equipped with a field
or factory-installed switch, it is compatible with electric gas line or appliance shut-off
devices.
Regulated Actuator Assembly - When more than
two agent tanks are required, the regulated actuator is available to provide expellant gas
for additional tanks. It is connected to the cartridge receiver outlet of the regulated
release mechanism providing simultaneous agent discharge. It contains a regulated actuator
deadset at 100 psi (6.9 bar) with an internal relief of approximately 145 psi (10.0 bar).
The regulated actuator assembly contains a regulated actuator, regulator, expellant gas
hose, and agent tank housed in a stainless steel enclosure with cover. The enclosure
contains knockouts to permit installation of the expellant gas line.
Discharge Nozzles - Each discharge nozzle is
tested and listed with the R-102 system for a specific application. Nozzle tips are
stamped with the flow number designation (1/2, 1, 2, and 3). Each nozzle must have a metal
or rubber blow-off cap to keep the nozzle tip orifice free of cooking grease build-up.
APPROVALS
Applicable Standards: ULI listed under EX-3470; ULC listed under CEX-747; meets
requirements or NFPA 96 (Standard for the Installation of Equipment for the Removal of
Smoke and Grease-Laden Vapors from Commercial Cooking Equipment); NFPA 17A (Standard on
Wet Chemical Extinguishing Systems).
ORDERING INFORMATION
Order all system components through your local authorized Ansul Distributor.
SPECIFICATIONS
An Ansul R-102 Fire Suppression System shall be furnished. The system shall be capable
of protecting all hazard areas associated with cooking equipment.
GENERAL
| 1.1 |
References |
|
|
1.1.1 |
Underwriters Laboratories, Inc. (UL) |
|
|
1.1.1.1 UL Standard 1254 |
|
|
1.1.1.2 UL Standard 300 |
|
1.1.2 |
National Fire Protection Association (NFPA) |
|
|
1.1.2.1 NFPA 96 |
|
|
1.1.2.2 NFPA 17A |
|
|
|
| 1.2 |
Submittals |
|
|
1.2.1 |
Submit two sets of manufacturer's data sheets |
|
1.2.2 |
Submit two sets of piping design drawings |
|
|
| 1.3 |
System Description |
|
1.3.1 |
The system shall be an automatic fire suppression system
using a wet chemical agent for grease related fires. |
|
1.3.2 |
The system shall be capable of suppressing fires in the
following areas associated with cooking equipment: ventilating equipment including hoods,
ducts, plenums, and filters; fryers; griddles and range tops; upright, natural charcoal,
or chain-type broilers; electric, lava rock, mesquite or gas-radiant char-broilers. |
|
1.3.3 |
The system shall be the pre-engineered type having minimum
and maximum guidelines established by the manufacturer and listed by Underwriters
Laboratories, Inc. (UL). |
|
1.3.4 |
The system shall be installed and serviced by personnel
trained by the manufacturer. |
|
|
| 1.4 |
Quality Control |
|
1.4.1 |
Manufacturer: The R-102
Restaurant Fire Suppression System shall be manufactured by a company with at least thirty
years experience in the design and manufacture of pre-engineered fire suppression systems.
The manufacturer shall be ISO 9002 registered. |
|
1.4.2 |
Certificates: The wet agent
shall be a specially formulated, aqueous solution of organic salts with a pH range between
7.8 - 8.2, designed for flame knockdown and foam securement of grease-related fires. |
|
|
| 1.5 |
Warranty: Disclaimer
and Limitations |
|
1.5.1 |
The pre-engineered restaurant fire suppression system
components shall be warranted for five years from date of delivery against defects in
workmanship and materials. |
|
|
|
| 1.6 |
Delivery |
|
|
1.6.1 |
Packaging: All system
components shall be securely packaged to provide protection during shipment. |
|
|
| 1.7 |
Environmental
Conditions |
|
1.7.1 |
The R-102 system shall be capable of operating in a
temperature range of 32 oF to 130 oF (0 oC to 54 o.
|
Product
| 2.1 |
Manufacturer |
|
|
2.1.1 |
Ansul Fire Protection, One Stanton Street, Marinette,
Wisconsin 54143-2542, Telephone (715) 735-7411. |
|
|
|
| 2.2 |
Components |
|
|
2.2.1 |
The basic system shall consist of an ANSUL AUTOMAN
regulated release assembly which includes a regulated release mechanism and a wet chemical
storage tank housed within a single enclosure. Nozzles, blow-off caps, detectors,
cartridges, agent, fusible links, and pulleys elbows shall be supplied in separate
packages in the quantities needed for fire suppression system arrangements. Additional
equipment shall include remote manual pull station, mechanical and electrical gas valves,
pressure switches, and electrical switches for automatic equipment and gas line shut-off. |
|
2.2.2 |
Wet Chemical Agent: The
extinguishing agent shall be a specially formulated, aqueous solution of organic salts
with a pH range between 7.8 - 8.2, designed for flame knockdown and foam securement of
grease related fires. |
|
2.2.3 |
Agent Tank: The agent tank
shall be installed in a stainless steel enclosure or wall bracket. The tank shall be deep
drawn carbon steel finished in red enamel. Tanks shall be available in two sizes; 1.5
gallon (5.7 L) and 3.0 gallon (11.4 L). The tanks shall have a working pressure of 100 psi
(6.9 bar), a test pressure of 300 psi (20.7 bar), and a minimum burst pressure of 600 psi
(41.4 bar). The tank shall include an adaptor/tube assembly containing a burst disc union.
|
|
2.2.4 |
Regulated Release Mechanism: The
regulated release mechanism shall be a spring-loaded, mechanical/pneumatic type capable of
providing the expellant gas supply to one or two agent tanks depending on the capacity of
the gas cartridge used. It shall contain a factory installed regulator deadset at 100 psi
(6.9 bar) with an internal relief of approximately 145 psi (10.0 bar) |
|
|
It shall have the following actuation capabilities:
automatic actuation by a fusible link detection system and remote manual actuation by a
mechanical pull station. |
|
|
The regulated release mechanism shall contain a release
assembly, regulator, expellant gas hose, and agent storage tank housed in a stainless
steel enclosure with cover. The enclosure shall contain knock-outs for 1/2 in. conduit.
The cover shall contain an opening for a visual status indicator. |
|
|
It shall be compatible with mechanical gas shut-off
devices; or, when equipped with a field or factory-installed switch, it shall be
compatible with electric gas line or appliance shut-off devices. |
|
2.2.5 |
Regulated Actuator Assembly:
When more than two agent tanks are required, the regulated actuator shall be available to
provide expellant gas for additional tanks. It shall be connected to the cartridge
receiver out-let of the regulated release mechanism providing simultaneous agent
discharge. The regulator shall be deadset at 100 psi (6.9 bar) with an internal relief of
approximately 145 psi (10.0 bar). The regulated actuator assembly shall contain a
regulated actuator, regulator, expellant gas hose, and agent tank housed in a stainless
steel enclosure with cover. The enclosure shall contain knockouts to permit installation
of the expellant gas line. |
|
2.2.6 |
Discharge Nozzles: Each
discharge nozzle shall be tested and listed with the R-102 system for a specific
application. Nozzle tips shall be stamped with the flow number designation (1/2, 1, 2, and
3). Each nozzle shall have a metal or rubber blow-off cap to keep the nozzle tip orifice
free of cooking grease build-up. |
|
2.2.7 |
Distribution Piping: Distribution piping shall be Schedule 40 black iron,
chrome-plated, or stainless steel pipe conforming to ASTM A120, A53, or A106. |
|
2.2.8 |
Detectors: The detectors
shall be the fusible link style designed to separate at a specific temperature. |
|
2.2.9 |
Cartridge: The cartridge
shall be a sealed steel pressure vessel containing either carbon dioxide or nitrogen gas.
The cartridge seal shall be designed to be punctured by the releasing device supplying the
required pressure to expel wet chemical agent from the storage tank. |
IMPLEMENTATION
| 3.1 |
Installation |
|
3.1.1 |
The R-102 fire suppression system shall be designed,
installed, inspected, maintained, and recharged in accordance with the manufacturer's
listed instruction manual. |
| 3.2 |
Training |
|
|
3.2.1 |
Training shall be conducted by representatives of the
manufacturer. |
|